Caratteristiche tecniche

Fattore K
4
Dati tecnici modelli standard
10-2500 kVA

DZN0 K4

Codice
Potenza
Frequenza
Perdite a vuoto
Perdite a carico
Rendimento
Classe di isolamento
DZN0 K4 10
10
50
160
460
94.2
H
DZN0 K4 12
12
50
180
560
94.2
H
DZN0 K4 15
15
50
190
710
94.3
H
DZN0 K4 20
20
50
225
770
95.3
H
DZN0 K4 25
25
50
260
920
95.5
H
DZN0 K4 30
30
50
290
1070
95.7
H
DZN0 K4 40
40
50
375
1340
95.9
H
DZN0 K4 50
50
50
440
1580
96.1
H
DZN0 K4 63
63
50
480
1660
96.7
H
DZN0 K4 80
80
50
670
1820
97
H
DZN0 K4 90
90
50
730
1920
97.1
H
DZN0 K4 100
100
50
790
2030
97.3
H
DZN0 K4 110
110
50
830
2140
97.4
H
DZN0 K4 125
125
50
930
2400
97.4
H
DZN0 K4 140
140
50
980
2610
97.5
H
DZN0 K4 160
160
50
1030
2990
97.5
H
DZN0 K4 180
180
50
1180
3150
97.7
H
DZN0 K4 200
200
50
1280
3360
97.7
H
DZN0 K4 225
225
50
1380
3580
97.8
H
DZN0 K4 250
250
50
1530
3840
97.9
H
DZN0 K4 280
280
50
1570
4160
98
H
DZN0 K4 315
315
50
1730
4540
98
H
DZN0 K4 350
350
50
1850
4910
98.1
H
DZN0 K4 400
400
50
2020
5810
98.1
H
DZN0 K4 450
450
50
2240
6500
98.1
H
DZN0 K4 500
500
50
2400
7200
98.1
H
DZN0 K4 630
630
50
2970
8370
98.2
H
DZN0 K4 800
800
50
3200
9800
98.4
H
DZN0 K4 1000
1000
50
4320
11400
98.5
H
DZN0 K4 1250
1250
50
5280
13540
98.5
H
DZN0 K4 1600
1600
50
6600
16400
98.6
H
DZN0 K4 2000
2000
50
8100
19300
98.6
H
DZN0 K4 2500
2500
50
9600
22950
98.7
H