Technical specifications

Frequency
50Hz ±5% o 60Hz ±5%
Voltage regulation
IGBT controlled
Adjusting energy parameters
Independent phase control
Selectable target voltage
220-230-240V (L-N) / 380-400-415V (L-L)
Output voltage accuracy
±0.5%
Admitted load variation
Up to 100%
Admitted load imbalance [%]
100
Cooling
Forced ventilation
Ambient temperature
-25/+45°C
Storage temperature
-25/+60°C
Max related humidity
<95% (non condensing)
Admitted overload
150% 2sec
Colour
RAL 9005
Instrumentation
  • Output digital multimetre
Installation
Indoor
Overvoltage protection
  • Class II output surge arrestors
Additional protections
  • EMI/RFI filters
  • Input circuit breaker
  • Protection by-pass (automatic)
  • Maintenance by-pass (manual)

Aquarius plus ±20%/±15%

type
rated power
max input current
rated output current
Data Sheet
ETP20-20
20
36
29
ETP30-15
30
51
43
ETP30-20
30
54
43
ETP45-15
45
76
65
ETP45-20
45
81
65
ETP60-15
60
102
87
ETP60-20
60
109
87
ETP90-15
90
153
130
ETP90-20
90
162
130
ETP120-15
120
204
173
type
rated power
max input current
rated output current
Data Sheet
ETP10-30
10
20
14
ETP15-25
15
29
22
ETP15-30
15
31
22
ETP20-25
20
39
29
ETP20-30
20
41
29
ETP30-25
30
57
43
ETP30-30
30
61
43
ETP45-25
45
86
65
ETP45-30
45
93
65
ETP60-25
60
116
87