Technical specifications

Colour
RAL 7035
Protection degree
  • IP32 (for floor mount cabinet)
  • IP20 (for wall mount version)
  • IP54 (optional for floor mount)
Rated voltage
Ue=200V - 480V ± 10%
Frequency
50Hz / 60Hz ± 3Hz
Plant type / number of phases
3 phases, 3 wires or 3 phases, 4 wires
Main network distribution
TN or TT
Harmonic compensation
up to 50a, individually selectable
Cosphi pfc
from 0.7 inductive to 0.7 capacitive
Dynamic load balancing between phases
prevents neutral overloading
Rated current
60A for each module
Parallel units
  • up to 5 in the same cabinet, 300 A total
  • possibility of operation of several units in parallel
Response time
< 200μs
Overload capability
2.5 In (x 10ms)
Cooling
forced ventilation
Ambient temperature
from -10°C to +45°C full performance, derating up to 55°C
Relative humidity
<95%, non condensing
Altitude
2000m, 4000m max with derating
Switching frequency
24kHz
Inverter topology
3 levels IGBT switch for low losses
Current limit
rated current
Protections
protections against overload, shortcircuit, overheating, overvoltage and undervoltage
Grid resonancy detection
with blocking resonancy currents
Transformers current
no. 3 CTs rated from 100A/1A and 2500A/1A (not supplied)
Graphic interface
7” display touch screen unit for commissioning and monitoring. Includes Ethernet interface
Certificates
CE, ROHS

Wall-mounted version

part number
description
compensation current - wire [nr.]
compensation current - phase [a]
compensation current - neutral [a]
voltage (50-60hz) [v]
full load losses [w]
stand by losses [w]
weight
Data Sheet
FA43W060XXA0000
ACTIVEmatic FA43 W 60A
3
60
200V ... 480V (±10%)
900
50
96
FA43W120XXA0000
ACTIVEmatic FA43 W 120A
3
120
200V ... 480V (±10%)
1800
100
160
FA44W060XXA0000
ACTIVEmatic FA44 W 60A
4
60
180
200V ... 415V (±10%)
900
50
96
FA44W120XXA0000
ACTIVEmatic FA44 W 120A
4
120
360
200V ... 415V (±10%)
1800
100
160
part number
description
compensation current - wire [nr.]
compensation current - phase [a]
compensation current - neutral [a]
voltage (50-60hz) [v]
full load losses [w]
stand by losses [w]
weight
Data Sheet
FA43F060XXA0001
ACTIVEmatic FA43 F 60A
3
60
200V ... 480V (±10%)
900
50
95
FA43F120XXA0001
ACTIVEmatic FA43 F 120A
3
120
200V ... 480V (±10%)
1800
100
158
FA43F180XXA0001
ACTIVEmatic FA43 F 180A
3
180
200V ... 480V (±10%)
2700
150
410
FA43F240XXA0001
ACTIVEmatic FA43 F 240A
3
240
200V ... 480V (±10%)
3600
200
470
FA43F300XXA0001
ACTIVEmatic FA43 F 300A
3
300
200V ... 480V (±10%)
4500
250
530
FA44F060XXA0001
ACTIVEmatic FA44 F 60A
4
60
180
200V ... 415V (±10%)
900
50
96
FA44F120XXA0001
ACTIVEmatic FA44 F 120A
4
120
360
200V ... 415V (±10%)
1800
100
160
FA44F180XXA0001
ACTIVEmatic FA44 F 180A
4
180
540
200V ... 415V (±10%)
2700
150
413
FA44F240XXA0001
ACTIVEmatic FA44 F 240A
4
240
720
200V ... 415V (±10%)
3600
200
474
FA44F300XXA0001
ACTIVEmatic FA44 F 300A
4
300
900
200V ... 415V (±10%)
4500
250
535