code
|
puissance
|
courant d'appel
|
pertes à vide
|
pertes dépendantes
|
vcc
|
Fiche Produit
|
---|---|---|---|---|---|---|
DYN11 K4 CU IP00 10
|
10
|
32
|
150
|
430
|
3.5
|
|
DYN11 K4 CU IP00 12
|
12
|
32
|
170
|
530
|
3.5
|
|
DYN11 K4 CU IP00 15
|
15
|
32
|
180
|
660
|
3.5
|
|
DYN11 K4 CU IP00 20
|
20
|
30
|
210
|
720
|
3.5
|
|
DYN11 K4 CU IP00 25
|
25
|
30
|
240
|
860
|
3.5
|
|
DYN11 K4 CU IP00 30
|
30
|
25
|
270
|
1000
|
3.5
|
|
DYN11 K4 CU IP00 40
|
40
|
20
|
340
|
1060
|
4
|
|
DYN11 K4 CU IP00 50
|
50
|
18
|
400
|
1190
|
4
|
|
DYN11 K4 CU IP00 63
|
63
|
17
|
460
|
1350
|
4
|
|
DYN11 K4 CU IP00 80
|
80
|
15
|
530
|
1560
|
4
|
|
DYN11 K4 CU IP00 90
|
90
|
15
|
570
|
1680
|
4
|
|
DYN11 K4 CU IP00 100
|
100
|
14
|
610
|
1800
|
4
|
|
DYN11 K4 CU IP00 110
|
110
|
13
|
650
|
1930
|
4
|
|
DYN11 K4 CU IP00 125
|
125
|
13
|
700
|
2110
|
4
|
|
DYN11 K4 CU IP00 140
|
140
|
12
|
750
|
2290
|
4
|
|
DYN11 K4 CU IP00 160
|
160
|
12
|
820
|
2530
|
4
|
|
DYN11 K4 CU IP00 180
|
180
|
11
|
880
|
2770
|
4
|
|
DYN11 K4 CU IP00 200
|
200
|
11
|
940
|
3000
|
4
|
|
DYN11 K4 CU IP00 225
|
225
|
10
|
1010
|
3290
|
4
|
|
DYN11 K4 CU IP00 250
|
250
|
10
|
1080
|
3580
|
4
|
|
DYN11 K4 CU IP00 280
|
280
|
9
|
1160
|
3930
|
4
|
|
DYN11 K4 CU IP00 315
|
315
|
9
|
1250
|
4320
|
4
|
|
DYN11 K4 CU IP00 350
|
350
|
8
|
1340
|
4710
|
4
|
|
DYN11 K4 CU IP00 400
|
400
|
8
|
1460
|
5260
|
4
|
|
DYN11 K4 CU IP00 450
|
450
|
8
|
1570
|
5800
|
4
|
|
DYN11 K4 CU IP00 500
|
500
|
7
|
1670
|
6320
|
4
|
|
DYN11 K4 CU IP00 630
|
630
|
7
|
1930
|
7630
|
4
|
|
DYN11 K4 CU IP00 800
|
800
|
6
|
2250
|
9230
|
4
|
|
DYN11 K4 CU IP00 1000
|
1000
|
6
|
2580
|
10940
|
4.5
|