Technical specifications

Frequency
50
K Factor
13
Input voltage
400
Output voltage
400
Primary winding connection
Delta
Secondary winding connection
Zig-zag
Vector unit
Dzn0
Core material
M270 magnetic steel
Winding material
Aluminium
Electrostatic shield
Between primary & secondary, connected to ground
Max ambient temperature
40
Insulation class
H
Insulation level
3
Thermal class
H
Temperature rise
125
Max altitude
1000
Environmental - climate - fire class
E1 - C1 - F0
Installation
Indoor
Protection degree
  • IP00
Reference Standards
EN 60076 / IEC 61558 (when applicable)

DZN0 K13 A IP00

part number
power
in-rush current
no-load losses
load losses
vcc %
Data Sheet
DZN0 K13 A IP00 30
30
26
375
900
4
DZN0 K13 A IP00 40
40
16
440
1070
4
DZN0 K13 A IP00 50
50
16
480
1160
4
DZN0 K13 A IP00 63
63
16
670
1230
4
DZN0 K13 A IP00 70
70
16
730
1290
4
DZN0 K13 A IP00 80
80
16
790
1410
4
DZN0 K13 A IP00 90
90
13
830
1480
4
DZN0 K13 A IP00 100
100
13
930
1630
4
DZN0 K13 A IP00 110
110
13
980
1750
4
DZN0 K13 A IP00 125
125
13
1030
2000
4
DZN0 K13 A IP00 140
140
12
1180
2110
4
DZN0 K13 A IP00 160
160
12
1280
2260
4
DZN0 K13 A IP00 180
180
12
1380
2440
4
DZN0 K13 A IP00 200
200
11
1530
2580
4
DZN0 K13 A IP00 225
225
11
1570
2790
4
DZN0 K13 A IP00 250
250
11
1730
3040
4
DZN0 K13 A IP00 280
280
11
1850
3390
4
DZN0 K13 A IP00 315
315
10
2020
3840
4
DZN0 K13 A IP00 350
350
10
2240
4350
4
DZN0 K13 A IP00 400
400
9
2400
4830
4
DZN0 K13 A IP00 500
500
8
2970
5600
4
DZN0 K13 A IP00 630
630
7
3200
6590
4
DZN0 K13 A IP00 800
800
7
4320
7660
4.5
DZN0 K13 A IP00 1000
1000
7
5280
9000
4.5
DZN0 K13 A IP00 1250
1250
6
6600
11100
5
DZN0 K13 A IP00 1600
1600
5
8100
13100
5
DZN0 K13 A IP00 2000
2000
5
9600
15500
6