Technical specifications

Frequency
50
K Factor
4
Input voltage
400
Output voltage
400
Primary winding connection
Delta
Secondary winding connection
Zig-zag
Vector unit
Dzn0
Core material
M270 magnetic steel
Winding material
Copper
Electrostatic shield
Between primary & secondary, connected to ground
Max ambient temperature
40
Insulation class
H
Insulation level
3
Thermal class
H
Temperature rise
125
Max altitude
1000
Environmental - climate - fire class
E1 - C1 - F0
Installation
Indoor
Protection degree
  • IP21
Reference Standards
EN 60076 / IEC 61558 (when applicable)

DZN0 K4 R IP21

part number
power
in-rush current
no-load losses
load losses
vcc %
Data Sheet
DZN0 K4 R IP21 10
10
34
160
460
3.5
DZN0 K4 R IP21 12
12
34
180
560
3.5
DZN0 K4 R IP21 15
15
34
190
710
3.5
DZN0 K4 R IP21 20
20
32
225
770
3.5
DZN0 K4 R IP21 25
25
32
260
920
3.5
DZN0 K4 R IP21 30
30
27
290
1070
3.5
DZN0 K4 R IP21 40
40
21
330
1120
4
DZN0 K4 R IP21 50
50
19
360
1280
4
DZN0 K4 R IP21 63
63
16
410
1480
4
DZN0 K4 R IP21 80
80
15
470
1750
4
DZN0 K4 R IP21 90
90
14
510
1910
4
DZN0 K4 R IP21 100
100
13
540
2070
4
DZN0 K4 R IP21 110
110
12
580
2220
4
DZN0 K4 R IP21 125
125
12
630
2460
4
DZN0 K4 R IP21 140
140
11
680
2690
4
DZN0 K4 R IP21 160
160
10
740
3000
4
DZN0 K4 R IP21 180
180
10
810
3300
4
DZN0 K4 R IP21 200
200
9
870
3610
4
DZN0 K4 R IP21 225
225
9
940
3980
4
DZN0 K4 R IP21 250
250
8
1020
4360
4
DZN0 K4 R IP21 280
280
8
1100
4800
4
DZN0 K4 R IP21 315
315
7
1200
5310
4
DZN0 K4 R IP21 350
350
7
1290
5810
4
DZN0 K4 R IP21 400
400
6
1410
6510
4
DZN0 K4 R IP21 450
450
6
1520
7210
4
DZN0 K4 R IP21 500
500
6
1620
7880
4
DZN0 K4 R IP21 630
630
5
1840
9570
4