Technical specifications

Frequency
50Hz ±5% o 60Hz ±5%
Adjusting energy parameters
Independent phase control
Selectable target voltage
from 210V to 240V (L-N) / from 364V to 416V (L-L)
Output voltage accuracy
±0,5%
Admitted load variation
Up to 100%
Admitted load imbalance [%]
100
Cooling
Natural ventilation (from 35°C aided with fans from 100kVA)
Ambient temperature
-25/+45°C
Storage temperature
-25/+60°C
Max related humidity
<95% (non condensing)
Admitted overload
200% 2min.
Harmonic distorsion
None introduced
Colour
RAL 7035
Installation
Indoor
Instrumentation
EnerCloud Platform
Additional protections
  • Electronic automatic by-pass system

Type
Rated power
Input voltage range [V]
Max input current
Related voltage
Max output current
VARIANT SHEET
45-5
45
Vout +10%
72
400
65
63-5
63
Vout +10%
101
400
91
100-5
100
Vout +10%
160
400
144
125-5
125
Vout +10%
200
400
180
160-5
160
Vout +10%
257
400
231
200-5
200
Vout +10%
321
400
289
250-5
250
Vout +10%
401
400
361
315-5
315
Vout +10%
505
400
455
400-5
400
Vout +10%
642
400
577
500-5
500
Vout +10%
802
400
722
630-5
630
Vout +10%
1010
400
909